TL;DR
- The blockage is a heat problem. A walk-in cooler condenses room moisture onto the evaporator; when the drain path sits below freezing, that water plugs the line or trap and the next defrost discharges onto the floor.
- Our published drain pan heater loading is about 300–400 W per metre of tube, in stainless steel SUS304, SUS316 or SUS310S, with length and voltage set to the job.
- Shape follows the fitting. The published range covers single straight, A-A double straight tube, U shaped and L shaped for the water tray, in 6.5 mm, 8.0 mm and 10.7 mm tube.
- Sealing decides survival. IP65 is standard; IP67 is available with a silicone rubber seal head in 8.7 mm, 9.0 mm and 9.5 mm diameters.
- Control decides usefulness. A pan heater on a continuous timer is a different product from one sequenced with the defrost cycle, and that choice belongs to the cooler.
Most walk-in cooler service calls reported as water on the floor are not leaks. They are drain lines that stopped draining: the condensate is still produced at the same rate, but somewhere between the pan and the floor drain there is now a plug of ice, and every defrost cycle after that adds more water than the line can carry away.
Where the ice actually forms in a walk-in cooler
Every walk-in cooler is a humidity engine, and the drain line is where the water leaves it. Warm, moist room air meets an evaporator coil sitting below the dew point of that air, water condenses on the fins, and it runs down into the pan. In a working cooler that water leaves on every defrost cycle. The failure is not that the water appears; it is that the water appears and cannot leave.
Two places block, for different reasons. The first is the pan and the trap below it, where cold coil and cold metal can hold the water below the freezing point of the room. The second is the horizontal run of the drain line, where the same water sits with no airflow and no heat around it. In a box held around 2 to 4 °C the margin against freezing at those surfaces is thin, and a unit cooler that is slightly under-piped will find it.
This article is about selection, not site diagnosis. A pan heater does not fix a badly graded drain line, a blocked floor drain or a unit cooler short of capacity, and I would rather say that than sell a part into a problem it cannot solve. Because the heater is only one part of the path, so it is worth specifying it properly rather than fitting the cheapest tube that reaches the pan.
What a drain pan heater actually does on a unit cooler
Our published drain pan heater is a stainless steel tube element for the water tray of a unit cooler, with a published loading of about 300 to 400 W per metre for defrosting, tube material in SUS304, SUS316 or SUS310S, and length and voltage customised. The specification is deliberately short: the element follows the pan rather than arriving as a finished assembly with a fixed rating.
The shape follows the fitting it has to live in. The published unit cooler range covers a single straight shape, an A-A type with two straight tubes, a U shape and an L shape used for the water tray, in tube diameters of 6.5 mm, 8.0 mm and 10.7 mm. In a pan this matters more than on a coil: a pan has a rim, a corner and a fall, and an element that has to be bent on site should have been bent at the factory.

Our evaporator heater is a different component and should not be confused with it: a Cr20Ni80 nickel-chromium core inside a 304 stainless steel pipe with high-density magnesium oxide insulation between them, in U, straight or irregular shapes, with IP65 sealing, insulation resistance of at least 100 MΩ, CE and RoHS certification and a published lifespan of at least 8,000 hours. It sits in the coil and removes frost; the drain pan heater sits in the pan and keeps the water moving, so sizing one against the other is the most common error on enquiry forms.
Selecting the tube: alloy, diameter and length
The first choice is the alloy, a choice about the water rather than the temperature. A drain pan is permanently wet and cold, which is what attacks stainless: chloride in the condensate and oxygen at the water line. Our published options are SUS304, SUS316 and SUS310S, and we publish a walk-in freezer element in 304, 316 and 310S for the harsh high-humidity, low-temperature environment of a walk-in freezer. Because 316 carries molybdenum and resists chloride pitting better than 304, so a coastal unit, a brine washdown or salt tracked in on pallets is where the upgraded alloy pays.
The second choice is tube diameter, set by the space available. The published diameters are 6.5 mm, 8.0 mm and 10.7 mm. A thinner tube bends more easily into a tight corner and fits around a drain boss; a thicker tube carries more watts per metre at the same surface temperature. Because the pan heater runs wet, so its surface temperature decides whether it melts a plug or cooks the water it should move.
The third choice is length, and it is arithmetic. At a published loading of 300 to 400 W per metre, a one metre element is a 300 to 400 W load, so element length and wattage are one decision taken twice. The published convention for the double tube unit cooler element is that the tube length follows the evaporator fin length; the same applies in a pan, where the element should cover the pan floor and the trap. Because a heater sized to the width of the pan can leave the corners and the trap below freezing, so the length should be set against the wetted path.
Rule of thumb from our published figures: measure the wetted path from the drain boss to the trap outlet, multiply by the published 300 to 400 W per metre, then check that the wattage lands on a circuit the cooler already has.
Sealing, leads and the wet environment
A drain pan heater lives in water, so the sealing is not a detail. Standard sealing on our defrost heater range is IP65. For harsher environments we publish an IP67 version with a silicone rubber seal head, in 6.5 mm and 8.0 mm tube, with rubber head diameters of 8.7, 9.0 and 9.5 mm. Because the termination is the one place where the element is deliberately in contact with the wet pan, so the head that terminates it decides whether the element survives the season.
The lead wire is where most retrofit jobs are decided, because it is the part that has to reach the panel. The published conventions are specific: on the double tube unit cooler element the connection wire with two straight tubes is 250 mm or 300 mm with a standard 800 mm lead, while on the static evaporator element the connect wire is about 200 to 300 mm with 200 mm as the standard. All of it is customisable, and the practical question in a retrofit is whether the existing junction box is close enough for a standard lead to reach, because a heater that needs a new cable run is a different job from one that needs a bracket.
Protection and earthing complete the installation, and both belong in the specification. Our published heater for Fisher and Paykel type refrigeration, for example, carries two 72 degree fuses, and that range is published at 460 mm, 520 mm and 560 mm, 110 to 230 V. Because a heater that has lost its earth will eventually take the case live, and a drain pan is where nobody looks at the terminations after commissioning.
Control: when the heater runs decides whether it works
The heater is half of the decision, and the control strategy is the half people argue about. A pan heater on a continuous timer keeps the pan above freezing all day, the simplest strategy and the most expensive, because the element draws its full rating for the whole day. A heater sequenced only with the defrost cycle costs far less energy and leaves the line unprotected between cycles, acceptable in some boxes and not others.
US energy conservation rules treat defrost control as part of the equipment rather than an accessory. 10 CFR Part 431, Subpart R covers walk-in coolers and walk-in freezers, and its definitions section defines adaptive defrost as a factory-installed defrost control system that reduces defrost frequency by initiating defrosts or adjusting the number of defrosts per day in response to operating conditions such as moisture levels in the refrigerated space or coil frost load, rather than initiating defrost strictly on compressor run time or clock time. Because the defrost strategy is a regulated property of the appliance, so the pan heater’s logic belongs in the same specification as the coil heater’s.
For the EU the split is between storage and display. Commission Regulation (EU) 2019/2024 lays down ecodesign requirements for refrigerating appliances with a direct sales function, covering the display case route rather than walk-in storage, and Directive 2009/125/EC is the framework act those requirements sit under. Because the same heater can arrive in two very different compliance packages, so the sales route has to be settled before the documentation is assembled.
What to write in the purchase specification
Most heater enquiries arrive as a message asking for a drain heater, and the reply has to be questions. The specification that saves a round trip contains: material grade and tube diameter, element length along the wetted path, wattage from the published 300 to 400 W per metre band, supply voltage at the junction box, sealing and lead length, the shape that fits the pan, and the fuse and earthing arrangement. Because the element is made to order with length and voltage customised, so a specification that leaves the length open returns a quotation that cannot be compared with any other.
| Parameter | Published option | What it decides |
|---|---|---|
| Loading | About 300 to 400 W per metre | Element wattage and the circuit it lands on |
| Tube diameter | 6.5 mm, 8.0 mm, 10.7 mm | Bendability in the pan, watts carried per metre |
| Shape | Single straight, A-A double tube, U shaped, L shaped for the water tray | How the element sits in the pan |
| Sealing | IP65 standard; IP67 with silicone rubber seal head in 8.7, 9.0 and 9.5 mm | Whether the termination survives a wet pan |
| Leads | 250 mm or 300 mm connection wire with 800 mm standard lead; 200 to 300 mm with 200 mm standard on the static evaporator element | Whether the panel is reachable without new cable |
| Protection | Two 72 degree fuses on the published Fisher and Paykel type element | Fault protection in a wet metal pan |
Two questions settle the job faster than any datasheet. The first is whether the drain line runs above freezing all year in that room, because a heated sub-base or warm return air duct may solve it without an element. The second is how the cooler is controlled. Send us the pan dimensions, the drain run length, the supply voltage and the control arrangement through the contact page, and we will come back with the element that fits your pan.
Frequently Asked Questions
Why does a walk-in cooler drain line freeze when the room itself is warm?
Because the drain line is colder than the room. The coil and the pan sit below the dew point of the air entering the box, so water forms on them continuously, and the pan and trap are the coldest surfaces in the room. Water in a cold trap with no airflow can drop below freezing even when the room is well above it, and the plug turns the next defrost into water on the floor.
What wattage does a drain pan heater need?
Our published loading is about 300 to 400 W per metre, so the wattage follows the element length. Measure the wetted path, from the drain boss along the pan floor into the trap, and multiply: a one metre element is a 300 to 400 W load. The wattage is the circuit, so check the supply at the junction box before specifying.
Is IP65 sealing enough for a drain pan?
IP65 is our standard sealing on the defrost heater range, and right in a dry, clean pan. In a wet, cool or washdown environment we publish an IP67 version with a silicone rubber seal head, in 6.5 mm and 8.0 mm tube, with rubber head diameters of 8.7, 9.0 and 9.5 mm. The termination is the one place the element sits in the water.
Should a drain line heater run continuously or only during defrost?
Continuous running is simplest and most expensive, because the element draws its full rating all day. Sequencing it with the defrost cycle costs less energy but leaves the line unprotected between cycles. This is a property of the cooler’s control strategy, and in the US 10 CFR Part 431 Subpart R treats defrost control as part of the regulated walk-in equipment, so decide it at specification stage.
Can a drain pan heater be retrofitted to an existing unit cooler?
Yes, and our published range is built for it: length, voltage and shape are customisable, and we publish four shapes including the L shape for the water tray. The practical constraints are the supply voltage at the existing panel, the reach of the lead wire and the space along the pan floor. Send the pan dimensions and a photograph of the terminal board and we will say whether it is a bracket job or a new circuit.
Which material should the tube be in a wet, cold environment?
Our published options are SUS304, SUS316 and SUS310S, and the walk-in freezer element in our range is built in 304, 316 and 310S for the high-humidity, low-temperature environment of a walk-in freezer. In short, 316 carries molybdenum and resists chloride pitting better, which matters for coastal sites, brine or salt tracked in, while a dry inland box runs 304 without trouble.
About the Author
Jake is Product Manager at Shengzhou Jingwei Electric Heating Appliance Co., Ltd., producing defrost heater tube, oven heating elements, finned heating elements, electric heating tubes, silicone rubber heaters including heating pads, silicone heating belts, crankcase heaters and drain line heaters, aluminium foil heaters and aluminium heating plates. Follow the company on Facebook and YouTube.